Effectively restrain harmonic current, improve the power factor of the whole machine, effectively restrain the current impact caused by the sudden change of grid voltage and over-voltage, improve the interference of the power supply to other equipment, and improve the unbalanced voltage between power supply phases that is greater than the rated voltage
Technical Data | |
Rated Voltage: | 380V/440V |
Operation Frequency: | 50/60HZ |
Rated Current: | 3A-1600A |
Hi-pot Test: | 3.5kV, 60sec |
Insulation Class: | F or above |
Reactor Impedance: | 2% |
Ambient temperature: | -25^ to 401: |
Protection Category: | I POO |
Design corresponding to Standards: | GB19212.1-2008 / GB19212.21-2007 /GB1094.6-2011 |
Application Schematic
Outline dimension drawing
Type Selection Table |
|||||||
|
|
(mH) |
(A) |
m(m) Dimensions 1 |
|||
Model |
Power (KW) |
Inductance |
Rated Current |
L |
W |
H |
Installation dimensions E*F |
5A |
1.5 |
2.80 |
5 |
160 |
120 |
140 |
80*60 |
7A |
2.2 |
2.00 |
7 |
160 |
120 |
140 |
80*60 |
10A |
3.7 |
1.40 |
10 |
160 |
120 |
140 |
80*60 |
ISA |
5.5 |
0.93 |
15 |
160 |
120 |
140 |
80*60 |
20A |
7.5 |
0.70 |
20 |
160 |
120 |
140 |
80*60 |
30A |
11 |
0.47 |
30 |
160 |
120 |
140 |
80*60 |
40A |
15 |
0.35 |
40 |
160 |
120 |
140 |
80*60 |
50A |
18.5 |
0.28 |
50 |
160 |
130 |
140 |
80*75 |
60A |
22 |
0.24 |
60 |
160 |
140 |
140 |
80*85 |
80A |
30 |
0.17 |
80 |
190 |
150 |
160 |
80*85 |
90A |
37 |
0.16 |
90 |
190 |
150 |
160 |
80*85 |
120A |
45 |
0.12 |
120 |
190 |
150 |
160 |
80*95 |
150A |
55 |
0.09 |
150 |
225 |
160 |
190 |
120*85 |
200A |
75 |
0.07 |
200 |
225 |
160 |
220 |
120*85 |
220A |
90 |
0.064 |
220 |
225 |
170 |
220 |
120*95 |
250A |
110 |
0.056 |
250 |
225 |
180 |
220 |
120*95 |
290A |
132 |
0.047 |
290 |
260 |
160 |
250 |
135*85 |
330A |
160 |
0.042 |
330 |
260 |
170 |
250 |
135*95 |
390A |
185 |
0.036 |
390 |
260 |
170 |
250 |
135*95 |
440A |
200 |
0.032 |
440 |
260 |
170 |
250 |
135*95 |
490A |
220 |
0.028 |
490 |
260 |
180 |
250 |
135*95 |
540A |
250 |
0.025 |
540 |
290 |
200 |
310 |
135*95 |
600A |
280 |
0.023 |
600 |
290 |
210 |
310 |
135*95 |
700A |
315 |
0.021 |
700 |
290 |
210 |
310 |
135*105 |
800A |
350 |
0.018 |
800 |
290 |
220 |
310 |
135*125 |
1000A |
400 |
0.014 |
1000 |
290 |
230 |
310 |
Note: The above specifications are the company’s standard products, and the product performance, size and appearance can be customized according to the customer’s products.
Product Display
Product detail pictures:
Related Product Guide:
Our organization sticks to your principle of Quality may be the life of your organization, and reputation will be the soul of it for 2021 New Style Three Phase Current Transformer - Three phase AC Type input reactor – Xinping , The product will supply to all over the world, such as: Cologne, Holland, Milan, Providing the best products, the most perfect service with the most reasonable prices are our principles. We also welcome OEM and ODM orders.Dedicated to strict quality control and thoughtful customer service, we are always available to discuss your requirements and ensure full customer satisfaction. We sincerely welcome friends to come negotiate business and start cooperation.
By Ivy from Jordan - 2017.04.18 16:45
This manufacturers not only respected our choice and requirements, but also gave us a lot of good suggestions, ultimately, we successfully completed the procurement tasks.
By Rose from Tunisia - 2018.09.21 11:44